690V Active Harmonic Filter
Active Harmonic Filter
Optimize your harmonic filtering efficiency: the 3-Level Topology Design Approach
Active harmonic filters are based on power electronic technology, designed for mitigating harmonics injected by non-linear loads in power networks. Generally installed in parallel to the polluting loads, the active filters analyze the line current harmonics drawn by the loads and generates a compensation current at the opposite phase angle, thereby “neutralizing” the harmonic currents.
Incorporating the 3-level topology design, Sinexcel active harmonic filters (AHF series) are the ideal, comprehensive solution, offering an optimal harmonic filtering efficiency, load balancing and reactive power compensation for applications of all types. Its compact high performance is testified by a track record of more than 120,000A installations.
Key features
The Sinexcel Modular Active Harmonic Filter series are suitable for applications of all types, providing harmonic mitigation, load balancing and step-less reactive power compensation for inductive and capacitor loads.
Optimized harmonics filtering efficiency
Selection of every harmonic to the 50th order /Filter up to 50 harmonics simultaneously /Harmonic filtering levels [%] can be pre-configured for each harmonic order in specific/Resonance protection by means of pre-configuring harmonic filtering levels for the potential resonance zones/Harmonic attenuation > 97%
Compact high performance
Ultra-compact, space economical/User-friendly, ease of commissioning/Parallel capability of modular AHF units with respect to network requirements/Available in rack, wall mounting designs and complete enclosure type
Enhanced Reliability Levels
Incorporates intelligent FFT calculation method
Provides “real time sensing” of network impedance for progressive harmonics compensation to achieving system stability/ Advanced control algorithm for resonance protection/ In event of parallel resonance with load variations, the AHF is designed to assess and “shut-down” to avoid equipment damage
Provide wide ranging protection modes:
Internal temperature diagnostic function to avoid overheating of internal components /internal short circuit /Overload protection/ CT reverse polarity and wrong configuration of CT settings
Segregated cooling design
Internal component groups are partitioned in 2 parts, i.e. circuit boards and heat producing elements. The former group will be of natural cooling and dust-protected whereas the latter group will include ventilation fan for effective heat dissipation.
Specification sheet
Model | 400V | 690V | ||
Sinexcel 025/035 | Sinexcel 050/060 | Sinexcel 100 | Sinexcel 075/150/225/300 | |
System parameters | ||||
Network Config. | 3P3W, 3P4W | 3P3W | ||
Parallel operation | Unlimited (up to 600A/cabinet c/w centralized monitoring PQ viewer, up to 300A for 690V series) | |||
Mains voltage | 400 VAC, -43%~+14% | 690 VAC, -30%~+10% | ||
Mains frequency | 45~63 Hz | |||
CT Setting | 150/5 … 10,000/5 | |||
Filter characteristics | ||||
Topology design | 3-level | |||
Rated compensation capacity | 25A/35 A | 50A/60A | 100A | 75A/150A/225A/300A |
Neutral compensation capacity | 3 times rating | without neutral | ||
Harmonics spectrum | 2nd~50th harmonic order | |||
Harmonics selectable | 2nd~50th harmonic order, all can be selected simultaneously | |||
Filtering degree | Programmable per harmonic from 10% to 110% | |||
Filter performance | THDi <5% | |||
Resonance Protection | Yes | |||
Power loss | <3% of rated power | <2% of rated power | ||
Switching frequency | 20 kHz | 18 kHz | ||
Reaction time | < 100 µs | < 300 µs | ||
Response time | < 10 ms | |||
Cooling air requirement | 270 m³/h | 544m³/h | 1080 m³/h | 2100 m³/h |
Noise level | < 54 dB | < 56 dB | < 58 dB | <60 dB |
Modes of Operation | Harmonic compensation (FFT analysis, instantaneous reactive power) | |||
Reactive power compensation (Target PF from -1 ~ 1) | ||||
Load balancing | ||||
Communication Capability | ||||
Interfaces | RS485 (Modbus RTU), TCP/IP (Ethernet) | RS485 (Modbus RTU), TCP/IP (Ethernet), USB | ||
Digital I/O | 4 digital inputs / 6 digital outputs | |||
Alarm events | Yes | |||
Monitoring | Via centralized monitoring PQ viewer/PQ software (included) | |||
Physical details | ||||
Mounting Type | Wall / rack | Cabinet | ||
Approx. dimensions (W*D*H), mm | 260x455x200 | 440x590x200 | 440x575x232 | 800x600x2200 |
Approx. weight | 16 kg | 35 kg | 40 kg | 210~480 kg |
Environmental conditions | ||||
Altitude | 1,500m/derating up to 4,000m, 1% / 100m | |||
Ambient temperature | -5°C~+45°C | -10°C~+40°C | ||
Relative humidity | Max.< 95%, non-condensing | |||
Protection class | IP20 | |||
Reference technical standards | ||||
Design / Approvals | IEC 61000-4-2, 4-3, 4-4, 4-5, 4-6, 4-8, 4-11, IEC 60146, EN 55011 Class A, EN 50091-1, EN 50178 | |||
Compliance with Standards | IEEE 519, IEC 61000-3-6, ER G5/4 | |||
* Other ratings can be achieved by combining the appropriate AHF units, | ||||
available in floor standing cabinet type c/w the PQ Viewer | ||||
* For 3P4W config. 3 sets of CT are required (at L1, L2 and L3) | ||||
For 3P3W config. 2 sets of CT are required (at L1 and L3) |